Gridley, CA Air Conditioning & Heating Services from Climate and Energy Solutions
From scheduling the service call or equipment installation, to the completion of the repair or new system install you are handled with honest, professional, affordable care. We are locally-owned, family-operated business that is a part of this community.
Check out what some of our customers are saying about Climate & Energy Solutions services.
Local Reviews
for Gridley, CA
Excellent
Will - Gridley, CA 95948
GridleyCA95948 39.3625-121.7025
great service
Brayden - Gridley, CA 95948
GridleyCA95948 39.355-121.7
Great guy and service
Iline - Gridley, CA 95948
Andrew was great!!! Explaining everything I needed to know about what was going on with the system. Took off screens covering vents to allow more air.
GridleyCA95948 39.3625-121.6875Great Service
Thomas - Gridley, CA 95948
GridleyCA95948 39.37-121.6925
Great job
Lynn - Gridley, CA 95948
GridleyCA95948 39.365-121.6975
Thank you
BC - Gridley, CA 95948
GridleyCA95948 39.365-121.6975
Knowledgeable and willing to answer any questions.
Matt - Gridley, CA 95948
GridleyCA95948 39.3475-121.65
Excellent service
1030 - Gridley, CA 95948
He was very friendly. He got right to the job and was able to right away identify the problem. Overall very great service!
GridleyCA95948 39.3575-121.695Good guys who do a good job!
Candy - Gridley, CA 95948
Andrew repaired our ailing and aging heater unit this afternoon. His steadfast attention to detail and giving professional feedback is always appreciated. I highly recommend him and the services of CES and Feather River Aire.
GridleyCA95948 39.3625-121.7075Excellent Service
Jake - Gridley, CA 95948
They were fast, courteous, and did a quality job at a fair price!
GridleyCA95948 39.365-121.685Excellent service, highly recommend!
Candy - Gridley, CA 95948
Great service, clear communication, and a technician who really cares about his work and his clients. Thanks, Andrew!
GridleyCA95948 39.3625-121.7075Helpful
Paul - Gridley, CA 95948
Explained and good detail of what I should do to keep up and maintain my heater did an amazing job
GridleyCA95948 39.37-121.69Great service
Andrew - Gridley, CA 95948
I had someone come out and look at my heater was very helpful in explaining what was going on
GridleyCA95948 39.365-121.6925Fantastic service!!!
Lynn - Gridley, CA 95948
GridleyCA95948 39.365-121.6975
Much appreciated.
Butte - Gridley, CA 95948
Thank you for your help and keeping us updated with the status of our heating issue. it was much appreciated. Price I can't comment on as this is paid by someone else, but our Tech was so helpful.
GridleyCA95948 39.365-121.6975Great service
Miguel - Gridley, CA 95948
GridleyCA95948 39.37-121.6925
Great Service!
Becky - Gridley, CA 95948
Our A/C stopped working on a weekend, I called on Sunday and left my info for a call back on Monday. First thing Monday morning I got a call, service was scheduled for the following morning. Tech arrived promptly and did a through inspection of the system, quickly identified the problem, explained what happened and repair was made immediately. The whole process was a breeze, and the tech was great! Thank you!
GridleyCA95948 39.365-121.715Great
Maria - Gridley, CA 95948
Andrew was very informative he answered all my questions and was polite and profesional it was an overall good experience
GridleyCA95948 39.3675-121.6925Great service
Miguel - Gridley, CA 95948
It was a great experience from start to finish. Andrew acted professionally & did a fantastic job.
GridleyCA95948 39.37-121.69Will
Will - Gridley, CA 95948
Awesome experience.
GridleyCA95948 39.3625-121.7On time. Polite. Knowledgeable
Ed - Gridley, CA 95948
GridleyCA95948 39.365-121.695
Jason H.
Single head mini split Mitsubishi30 K
Brenden W.
No ac. Found 45/5 capacitor on condenser has failed. Both sides at zero. Replaced with new capacitor which tests at 45.6/5.07. Compressor amp draw 6.46a, fan amp draw.54 amp. 237vac. 23° temperature split. Washed condenser coil.
Andrew R.
Performed preventative cooling maintenance on outdoor Amana AC condenser unit. Changed indoor air filter. Swapped out of range capacitor. Checked the following: -Amperages on compressor and outdoor condenser fan motor. -Dual run start capacitor for the compressor and fan. -Contactor and proper voltage. -Refrigerant circuit for proper flow. -Thermostat functionality. -Proper air flow/temperature split from supply and return vents. System is cooling well at this time with a temp split of 23°.
Andrew R.
Performed preventative cooling maintenance on outdoor Amana AC condenser unit. Changed indoor air filter. Checked the following: -Amperages on compressor and outdoor condenser fan motor. -Dual run start capacitor for the compressor and fan. -Contactor and proper voltage. -Refrigerant circuit for proper flow. -Thermostat functionality. -Proper air flow/temperature split from supply and return vents. System is cooling well at this time with a temp split of 23°.
Andrew R.
Thermostat was losing voltage frequently despite having new batteries. Replaced with new thermostat and system is now cooling well at this time.
Andrew R.
Performed preventative cooling maintenance on rooftop AC package unit. Changed indoor air filter. Checked the following: -Amperages on compressor and outdoor condenser fan motor. -Dual run start capacitor for the compressor and fan. -Contactor and proper voltage. -Refrigerant circuit for proper flow. -Thermostat functionality. -Proper air flow/temperature split from supply and return vents. System is cooling well at this time with a temp split of 16°.
Andrew R.
Performed preventative cooling maintenance on outdoor Lennox AC condenser unit. Changed indoor air filters. Checked the following: -Amperages on compressor and outdoor condenser fan motor. -Dual run start capacitor for the compressor and fan. -Contactor and proper voltage. -Refrigerant circuit for proper flow. -Thermostat functionality. -Proper air flow/temperature split from supply and return vents. System is cooling well at this time with a temp split of 16°.
Brenden W.
7/11- Replaced 12" and 16" dampers. Did not have the correct size bypass damper, got original functioning at about 60% (weighted style). Replaced blower wheel and sped up blower speed in AC. Reattached LAT sensor wire. 21° temperature split, 124/331, SH17 SC6, VSAT 42. Unit is running well.
Brenden W.
7/11- Replaced 12" and 16" dampers. Did not have the correct size bypass damper, got original functioning at about 60% (weighted style). Replaced blower wheel and sped up blower speed in AC. Reattached LAT sensor wire. 21° temperature split, 124/331, SH17 SC6, VSAT 42.
Brenden W.
HVAC No AC. Replaced ECM blower motor.
Brenden W.
HVAC No AC. Replaced ECM blower motor.
Brenden W.
HVAC No AC. Replaced ECM blower motor.
Brenden W.
HVAC No AC. Replaced ECM blower motor.
Brenden W.
Customer complains that AC works and then quits. Found that tenant had bypassed thermostat w jumper and apartment was 58°. Tested thermostat and found red>yellow circuit not always making. Maintenance to put on new stat. Tested condenser, SH 15 SC 8 157/310. Condenser very dirty, washed. Maintenance also previously changed the filter.
Alexander P.
Split system change out
Brenden W.
Unit seems to working correctly. No batteries in thermostat and time/date getting reset frequently. Customer uses the schedule function. Possibility that on the 2 days that the problem occurred, the thermostat was trying to follow the weekend schedule. New batteries installed. Customer will monitor and advise if problem persists.
Andrew R.
Removed dropped ceilng screens to improve airflow.
Andrew R.
Dual run capacitor was depleted, rusted, and ballooned. Replaced it and system is cooling well at this time. Operational Benchmarks: Capacitor: 35/5uf Compressor: 8.1a Outdoor Fan: .5a Temp Split: 80-63, 17°
Andrew R.
Performed preventative cooling maintenance on outdoor AC condenser unit. Changed indoor air filters. Checked the following: -Amperages on compressor and outdoor condenser fan motor. -Dual run start capacitor for the compressor and fan. -Contactor and proper voltage. -Refrigerant circuit for proper flow. -Thermostat functionality. -Proper air flow/temperature split from supply and return vents. System is cooling well at this time with a temp split of 16°.
Brenden W.
Summer maintenance. All specs are in range. 20°+ temperature split. New 20x25 filter.
Brenden W.
Summer maintenance. Roof package unit. All specs are in range. 20°+ temperature split. Reattached condensate line on roof.
Brenden W.
Summer maintenance.
Brenden W.
No AC. Low on freon and possible defective TXV.
Brenden W.
No AC. Summer maintenance.
Andrew R.
Performed an annual cooling maintenance on Carrier package heat pump. System was cooling well at this time, with a temp split of 18°. The capacitor, voltages, refrigerant pressures, amperages, wer all within range at this time.
Brenden W.
No AC. Only 3° temperature split. Low on refrigerant, possibly stolen. Added 4lbs 410A. 23° temperature split, SC 11.2.
Brenden W.
Assessing an older floor furnace.
Andrew R.
Replace an inducer assembly!
Andrew R.
Recharged a ductless minisplit!
Andrew R.
Diagnosed an overheating unit!
Andrew R.
Replaced a thermostat!